Standard Features
Membrane keypad:
· ADC-RES Controller
· Arrow keys step through generator set status displays
· Password-protected access to system configuration and
· adjustment menus
· System voltage/frequency selection and engine
· configuration
· Voltage, gain, and engine speed adjustment
LED display:
· Engine runtime, hours
· Output voltage, VAC
· Output frequency, Hz
· Battery voltage, VDC
· Crank cycle status
· Setup information
· Software version
Faults displayed:
· High battery voltage
· High engine temperature
· Low battery voltage
· Low oil pressure
· Overcrank
· Overfrequency
· Overspeed
· Overvoltage
· Underfrequency
· Undervoltage
Additional Features:
· Compact controller integrally mounted to the generator set
· Remote two-wire start/stop capability
· Digital isochronous governor to maintain steady-state speed
· Digital voltage regulation: ±1.5% RMS no-load to full-load
· Automatic start with programmed cranking cycle
· Field-upgradeable application software
· Front-access DB9 connector for software upgrade
· Generator set master switch (Run/Off-Reset/Auto)
· Engine Features
· Kohler Command PRO OHV engine with hydraulic valve lifters for reliable performance without routine valve adjustment or lengthy break-in requirements
· Simple field conversion between natural gas and LP vapor fuels while maintaining emission certification
· Digital Spark Advance Ignition (DSAI) optimizes engine performance for natural gas and LP vapor fuels
· Engine-mounted battery charging alternator
· Designed for Easy Installation
· Polymer base eliminates the need for a concrete
· mounting pad, reducing installation time and cost
· Fuel and electrical connections through the enclosure wall eliminate the need for stub-ups through the bottom
· Field-connection terminal block simplifies electrical connections
· Hinged roof with lockable latches
· Designed for outdoor installation only
· Certifications
· Meets emission regulations for U.S. Environmental Protection Agency (EPA) phase 2 small off-road engines and CA 2006 and later LSI engines with both
· LP vapor and natural gas
· UL 2200 listed
Transfer Switches
Model RDT Automatic Transfer Switch
· 200 Amps, 240 VAC, 60 Hz
· 2 pole, single phase
· Withstand short circuit rating 22,000 amps with specified breakers
· NEMA Type 3R enclosure
· UL 1008 listed
· Microprocessor-based transfer switch controls with fixed time delays
· Automatic engine start
· Engine cooldown (5 minutes)
· Weekly exercise function (20 minutes), loaded or unloaded
· Load control contact allows delayed connection of selected
· loads to the generator set (5 minutes)
· LED indicator shows:
· Exercise running
· Faults
· Dimensions, H x W x D:
· 613 x 340 x 177 mm (24.1 x 13.4 x 7.0 in.)
· Weight: 15 kg (33 lb.)
|